CVE-2020-25180

Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.

Score
CVSS 3.1 6.5 Medium
Status
Modified - ics-cert@hq.dhs.gov
Published
2022-03-18
Last modified
2025-04-16
Weaknesses
CWE-321, CWE-798

Affected products

References