CVE-2018-13815
A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
- Score
- CVSS 3.0 7.5 High
- Status
- Modified - productcert@siemens.com
- Published
- 2018-12-13
- Last modified
- 2024-08-05
- Weaknesses
- CWE-400, CWE-410
Affected products
- Simatic S7-1200 Firmware (Siemens)
- Simatic S7-1500 Firmware (Siemens)
- Simatic S7-1200 (Siemens Ag)
- Simatic S7-1500 (Siemens Ag)
References
- http://www.securityfocus.com/bid/105928
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdf